Kennel Ventilation


Appropriately made ventilation can minimize or get rid of odors, minimize bacteria buildup, and assistance preserve that fresh clean smell in the kennel. Your pets will be happier and you will commit much less time attempting to dry floors and eliminating the odors. If you have difficulty understanding details in this short article, e-mail us on the net at Sun Hill Pet Supplies.

No matter the size of your facility, ventilation will play a important part in the very first impression of guests to the kennel. Basically stated, ventilation is controlled, directed air movement.

Style fundamentals:

  1. Air exchanges: transform all of the air in the space 4 to six instances an hour. Calculate the space volume in cubic feet, multiply the outcome by 4, 5 or six, then divide by sixty to locate the air volume, in cfm (cubic feet per minute).
  2. Exhaust choose-up points: most kennel odors are developed at the similar level as the dogs so position your exhaust choose up points reduced than 30 inches to insure the odors are pulled downward, away from your nose. Having said that, not reduced than twelve inches from the floor to stop cleaning water from getting into the ventilation method.
  3. How several exhaust choose up points: Many points all through the space insure air movement has the likelihood to adequately circulate. Bear in mind we are not speaking about the return air duct to your heat method, we're speaking about exhaust vents to get rid of air from the space.
  4. Air provide: Set up your air provide vents, higher up in the space. This enables the air to flow downward to the exhaust choose up points, thereby pulling the odors down, and away from your nose. Bear in mind, provide air will have to be filtered and tempered, (heated or cooled), not be raw outdoors air. Your HVAC contractor can set up a unit that supplies enough fresh air into the ventilation method to meet the provide needs.
  5. Position of air provide and exhaust vents: Position the provide vents more than the aisle methods and the exhaust choose up points at the back of the runs in the walls or as pipes coming down the walls. If the heating supply is a “hot air” method, have a single third of the heated air introduced at the floor and two thirds introduced through the vents more than the aisle methods.
  6. Kind and design and style of the exhaust fan: You will want to use a blower with a centrifugal wheel as the air mover. Fans and blowers that use a blade comparable to that of a window fan will not be capable to overcome the static stress developed by the ductwork needed for many choose up points
  7. Size the blower: Generate a security issue by multiplying the cfm you calculated in step #1, by 1.five to insure your moving sufficient air, then opt for the exhaust blower to move that quantity of cfm at ½” of static stress or greater. Static stress is resistance to air flow, ordinarily developed by the duct method.
  8. Duct sizing: Higher air velocity in the method will insure excellent air flow so size the ducts for about 2000 fpm (feet per minute) air velocity. The easiest method to sizing is to identify the size of duct required to manage the total air flow, then, set up that size as the main duct, all through the creating. Identify the quantity of drops you want and divide the region of the main duct by the quantity of drops. Every single drop is then sized to that region. Use this formula to identify main duct size: (cfm / 1500fpm) x 144 = duct region in square inches